Rockwell Automation Publication 750-TD001H-EN-P - June 2013 9
PowerFlex 750-Series AC Drives
Technical Specifications
Category Specification
Protection
Motor Voltage
380/400 480V 600V 690V
AC Input Overvoltage Trip: 576V AC 576V AC 825V AC 825V AC
AC Input Undervoltage Trip: 250V AC 300V AC 400V AC 400V AC
Bus Overvoltage Trip: 815V DC 815V DC 1167V DC 1167V DC
Bus Undervoltage Shutoff:
Frames 1…7:
Frames 8…10:
200V DC
400V DC
200V DC
400V DC
200V DC (Frames 3…7)
400V DC
200V DC (Frames 6…7)
400V DC
Nominal Bus Voltage (Full Load): 540V DC 648V DC 810V DC 932V DC
Drive Overcurrent Trip
Software Overcurrent Trip:
Instantaneous Current Limit:
Hardware Overcurrent Trip:
200% of drive rated
100% of 3 sec. rating (158…210%)
143% of 3 sec. rating (215…287%)
Line transients: up to 6000 volts peak per IEEE C62.41-1991
Control Logic Noise Immunity: Showering arc transients up to 1500V peak
Power Ride-Thru: 15 milliseconds at full load
Logic Control Ride-Thru: 0.5 seconds minimum, 2 seconds typical
Ground Fault Trip: Phase-to-ground on drive output
Short Circuit Trip: Phase-to-phase on drive output
Electrical AC Input Voltage Tolerance: See page 11
for full power and operating range
Frequency Tolerance: 47…63 Hz
Input Phases: Three-phase input provides full rating for all drives. Single-phase operation on Frames 1…7 provides up to
50% of rated current at 25 °C (77 °F) surrounding temperature. Single-phase operation is not recommended
for Frames 8 and larger.
DC Input Voltage Tolerance: ±10% of Nominal Bus Voltage (above)
Displacement Power Factor: 0.98 across entire speed range
DC Link Impedance: ≥ 5%
Efficiency: 97.5% at rated amps, nominal line volts
Maximum Short Circuit Rating: 200,000 Amps RMS symmetrical (20F & 20G drives only)
Actual Short Circuit Rating: Determined by AIC rating of installed fuse/circuit breaker. See page 53
for 21G drives
Drive to Motor Power Ratio
Minimum:
Maximum:
Recommended not less than 1:2 ratio
Recommended not greater than 2:1 ratio
Brake IGBT Rating: 100% of motor rated torque
Control POD Current Draw: 5A
Digital Inputs
Nominal:
Maximum:
High State:
Low State:
DC
24V DC
30V DC
20…24V DC
0…5V DC
AC
120V AC
132V AC
100…132V AC
0…30V AC
Battery: User installed CR1220 lithium coin cell battery provides power to the real time clock (optional, not supplied).
Preserves the clock setting in the event power to the drive is lost or cycled. Approximate life is 4.5 years with
dive unpowered, or lifetime if drive is powered.